Main | |
Run time for load W information_stroke Min-max: 270-2700 W | 3min 58s |
Max. Capacity Used information_stroke | 100 % |
Main Input Voltage | 230 V |
Other Input Voltage | 220 V 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V 240 V |
rated power in W | 2700 W |
rated power in VA | 3000 VA |
Input Connection Type | BS1363A British IEC 60320 C20 Schuko CEE 7 / EU1-16P |
nb of power socket outlets | 8 IEC 60320 C13 2 IEC Jumpers 2 IEC 60320 C19 |
number of rack unit | 2U |
cable length | 2.44 m |
number of cables | 1 |
battery type | Lead-acid battery |
provided equipment | CD with software Documentation CD Installation guide Rack mounting brackets Rack mounting support rails USB cable Warranty card |
General | |
product web sub-family | High density |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
redundant | No |
Physical | |
colour | Black |
height | 8.5 cm |
width | 43.2 cm |
depth | 63.5 cm |
net weight | 31.3 kg |
mounting location | Front |
mounting preference | Lower |
mounting mode | Rack-mounted |
two post mountable | 0 |
USB compatible | Yes |
mounting position | Horizontal |
Input | |
network frequency | 40…70 Hz auto-sensing |
input voltage limits | 100…275 V adjustable (half load) |
Output | |
Maximum configurable power in W | 2700 W |
harmonic distortion | Less than 2 % |
output frequency | 50/60 Hz +/- 3 Hz sync to mains |
crest factor | 3 : 1 |
UPS type | Double conversion online |
Wave type | Sine wave |
bypass type | Internal bypass (automatic and manual) |
Maximum configurable power in VA | 3000 VA |
Conformance | |
product certifications | CE EAC RCM VDE |
marking | CE Mark |
standards | EN/IEC 62040-1 EN/IEC 62040-2 |
Environmental | |
ambient air temperature for operation | 0…40 °C |
relative humidity | 0…95 % non-condensing |
operating altitude | 0…10000 ft |
ambient air temperature for storage | -15…45 °C |
storage Relative Humidity | 0…95 % Non-condensing |
storage altitude | 0.00…15240.00 m |
acoustic level | 55 dBA |
heat dissipation | 703 Btu/h |
IP degree of protection | IP20 |
Batteries & Runtime | |
number of battery filled slots | 1 |
Battery recharge time | 3 h |
number of battery replacement quantity | 1 |
additional information | Configurable for 220 : 230 or 240 nominal output voltage |
battery voltage | 96 V |
battery charger power | 168 W rated |
Battery power in VAH | 505 VAh runtime |
battery life | 3…5 year(s) |
battery option | SRT96RMBP 1 1515 VAh SRT96RMBP 2 2525 VAh SRT96RMBP 3 3535 VAh SRT96RMBP 4 4545 VAh SRT96RMBP 5 5555 VAh SRT96RMBP 6 6565 VAh SRT96RMBP 8 8585 VAh SRT96RMBP 10 10605 VAh |
extended runtime | 1 |
Communications & Management | |
free slots | 1 |
control panel | Multifunction LCD status and control console |
alarm | Audible and visible alarms prioritized by severity |
Emergency power off | Yes |
Surge Protection and Filtering | |
Surge energy rate | 340 J |
Reviews